Where are Paprsky Energy storage systems manufactured?
In Dammam, Eastern Province, by Stralen Aero Company. Fabrication, coating, assembly and factory testing all take place in the Kingdom, which is what carries value under IKTVA and Local Content and Government Procurement Authority scoring. Local content is measured on value added inside the Kingdom, not on where the cell was made.
What battery chemistry do you use?
Lithium iron phosphate, known as LFP, selected for thermal stability, cycle life and cost. It is now the default chemistry for stationary storage worldwide. Cells are grade A from tier one manufacturers, supplied in matched batches so that capacity and internal resistance spread within a string stays tight.
What is the delivery lead time?
Typically 16 to 24 weeks from a confirmed order. The pace is set by cell and power conversion lead times rather than by factory capacity. Racks and cabinets can be quicker where modules are already held in stock, and we will tell you honestly which part of the schedule is fixed and which is not.
Will the systems hold up in Saudi summer conditions?
Containerized systems are liquid cooled and rated for 50 degrees Celsius ambient, with C5-M coating for coastal and marine sites. Cooling is sized against the design ambient temperature rather than a catalogue figure taken at 35 degrees, because an undersized chiller shortens cell life quietly and the damage only shows years later.
Do you supply battery racks separately from complete systems?
Yes, and it is a core part of what we do. Racks are available complete with busbar, harness, rack BMS and protection, as bare frames built to your drawing, as retrofit racks sized to replace an existing lead acid string in the same floor space, and as contract manufacture under your own part number and brand.
Which standards are the products designed and tested to?
IEC 62619, IEC 62933, UL 1973, UL 9540A, UN 38.3, NFPA 855 and NFPA 69, IEC 60529 IP55, ISO 12944 C5-M, the Saudi grid code, IEEE 1547, IEC 61850 and SASO conformity. Certification packs are prepared per project and per destination market, and we name individually the certificates we hold rather than making blanket claims.
What exactly is included in a ready to energise delivery?
The unit complete, internally wired, factory tested, with protection settings loaded, the energy management system configured to your grid code, full documentation and a spare parts list. You provide the foundation or plinth, the incoming and outgoing cables, the grid connection and utility approval, permits, crane access and the site earthing grid. The boundary is written into every quotation as a numbered list.
Can you support projects outside Saudi Arabia?
Yes. We ship across the Gulf from Dammam port, with export crating, UN 38.3 documentation and class 9 dangerous goods handling arranged through a certified forwarder. Commissioning and service outside the Kingdom is quoted per project.